Select a fan coil unit from the room's cooling load, then check that the unit's rated capacity, airflow, external static pressure and sound level suit your chilled water conditions and ceiling. This guide walks through the steps and reads real Daikin catalogue figures to show what they imply.

Start with the load, not the unit

A fan coil unit passes room air over a coil carrying chilled water, and over a hot-water coil where heating is needed. Its capacity must cover the cooling load of the room. Ask the consultant for the room's sensible load (the heat that raises air temperature) and latent load (the moisture that must be removed).

Then choose a unit whose catalogue capacity covers that load at your design conditions. Daikin links its professional selection software from its fan coils page for this purpose.

Six selection steps

  1. Capacity. Compare the room load with the unit's total and sensible cooling capacity at your chilled water and entering-air conditions.
  2. Airflow. Check the airflow at the fan speed you will actually run.
  3. External static pressure (ESP). For concealed units, the ductwork, grilles and filters set the resistance the fan must overcome.
  4. Coil arrangement. 2-pipe or 4-pipe, depending on whether areas must heat and cool at the same time.
  5. Sound level. Compare the sound pressure level at the speed and ESP you will use.
  6. Controls and valves. Thermostats, 2-way or 3-way valves with actuators and, where used, pressure independent control valves.

Reading a catalogue: Daikin FWW-VC figures

The table gives four sizes of Daikin's concealed-ceiling FWW-VC series (2-pipe, 3-row coil) from Daikin Middle East's FWW / FUW catalogue. The last column is not in the catalogue: we derived it from the water flow and capacity.

ModelAirflow, high (m³/h)Total cooling (kW)Sensible cooling (kW)Water flow (m³/h)Sound at 12 Pa, high (dB(A))Derived water ΔT (K)
FWW200VC3402.221.380.38355.0
FWW400VC6804.262.770.7340.55.0
FWW800VC1,3608.205.501.4144.55.0
FWW1400VC2,38013.009.202.23515.0

Catalogue figures: Daikin Middle East, FWW / FUW horizontal chilled water fan coil catalogue (CA-FCU H-202002), FWW-VC (AC) table. Derived ΔT uses flow x 4.19 kJ/kg.K (water, density about 1,000 kg/m³) and is an estimate; confirm the rating conditions in the catalogue.

How the derived column works: capacity = water mass flow x specific heat x temperature rise. For FWW200VC, 0.38 m³/h is about 0.106 kg/s; at 4.19 kJ/kg.K that is 0.442 kW per kelvin, so 2.22 kW implies a rise of about 5.0 K. The same arithmetic gives about 5 K for every size in the table.

What this tells you: the catalogue ratings are consistent with a 5 K chilled water temperature rise. If your system is designed for a different temperature rise, the water flow, capacity and pressure drop change, so re-select with the manufacturer's software instead of scaling the table.

Unit conversions used in this guide: 1 kW = 3,412 Btu/h; 1 TR (ton of refrigeration) = 3.517 kW; Daikin's catalogue uses 1 CFM = 1.7 m³/h.

Airflow and external static pressure

ESP is the resistance the fan can overcome in ductwork, grilles and filters. Daikin's FWW-VC series is rated at 12, 30 or 50 Pa. FWW-C and FWW-F are rated at 60 or 80 Pa, and FUW-A at 70 to 150 Pa depending on the model. Daikin's fan coils page lists ducted series with maximum ESP between 65 Pa and 250 Pa.

Choose the unit so that its available ESP at your fan speed covers the duct system in the ceiling, with margin for filter loading.

2-pipe or 4-pipe

A 2-pipe unit has one supply and one return pipe and carries either chilled or hot water at a time. A 4-pipe unit has separate chilled and hot circuits, so different areas can cool and heat together. In Daikin's FWW range, FWW-H is the 4-pipe version.

Schematic of a 2-pipe fan coil unit with one coil and a 4-pipe unit with a chilled coil and a hot coil.
2-pipe and 4-pipe fan coil coils, simplified.

Controls and valves

Thermostats, 2-way or 3-way valves with actuators and pressure independent control valves complete the unit. Daikin's catalogue states that the FWW-VC series can be fitted with a DC motor (DCBL) for stepless fan and valve control and connection to a building management system.

Selection checklist

  • Room sensible and latent load from the consultant
  • Chilled water supply and return temperatures, and entering-air condition
  • Total and sensible capacity at those conditions
  • Airflow at the planned fan speed
  • ESP available for the duct system, including filter loading
  • 2-pipe or 4-pipe
  • Sound level at the planned speed and ESP
  • Valve type, actuator and thermostat or BMS signal
  • Condensate drain route and service access

From our projects

A completed project related to this topic.

Design & supply of Daikin chilled water FCUs - Al Ansari Exchange Oasis Mall Dubai.

Design & supply of Daikin chilled water FCUs - Al Ansari Exchange Oasis Mall Dubai.

Successfully completed a prestigious project involving the design & supply of Daikin chilled water FCUs.With a successful track record in delivering cutting-edge…

Read the case study

Frequently asked questions

Divide kW by 3.517. A 13 kW unit is about 3.7 TR. In Btu/h, multiply kW by 3,412.

Related products

Sources

Technical claims on this page are attributed to the documents below. Figures quoted from manufacturers are the manufacturer's own, under its own test conditions. This page contains no prices or performance guarantees.

  1. Daikin Middle East: FWW / FUW horizontal chilled water fan coil unit catalogue (CA-FCU H-202002) Product lineup, FWW-VC (AC) technical table, nomenclature and conversion note
  2. Daikin Middle East: fan coils page Ducted series ESP ranges, selection software link
  3. Arithmetic by MEPTECH Derived water temperature rise: flow x specific heat of water (4.19 kJ/kg.K). Shown in the text so it can be checked.